NLW-1000

The NLW-1000 wide-range
logarithmic channel combines the functions of logarithmic counting
and logarithmic current conversion to provide a continuous indication
of reactor power from source level to full power. A remotely
located pre-amplifier minimizes EMI and other sources of interference
and adjustable discriminator and gain controls allow flexibility
in channel calibration with existing detectors. A differentiator
circuit provides continuous indication of rate of change of power,
and self test functions can sequentially check count rate, current,
period and high voltage. Provision is made for permissive operation
by computer of all test functions.
SPECIFICATIONS
NLW-1000 LOG WIDE-RANGE CHANNEL
| INPUT RANGE | Counting - 0.1 C/sec to 3x105 C/sec CURRENT 1x10-6 to 1x10-3 A | ||||||||||||||||||||
| LINEARITY (LOG CONFORMITY) + 1% OF THE LINEAR | Full scale equivalent covering the combined counting and current regions in the temperature range of 20°to 30°C | ||||||||||||||||||||
| TEMPERATURE COEFFICIENT | ± 0.15%/°C maximum over 10° to 55°C | ||||||||||||||||||||
| CALIBRATION/TEST | 2 fixed count rates, 2 fixed currents for calibration, 1 adjustable count rate, 1 adjustable current for trip testing, HV trip test, test modes selected sequentially by front panel control | ||||||||||||||||||||
| RESPONSE TIME CONSTANTS |
|
||||||||||||||||||||
| OUTPUTS |
|
||||||||||||||||||||
| BISTABLE TRIPS |
|
||||||||||||||||||||
| POWER REQUIRED | 117 VAC + 10% 50/60 Hz @ 1.0 A |